北京供暖季卧室环境与睡眠质量关联性研究

作者:王梅 张晓静 罗观璋 谢静超 刘加平
单位:北京工业大学
摘要:为了解卧室环境特点和居民睡眠状况,并探究两者之间的关联性,于供暖季在北京城镇地区随机调研了48名住户。测试期间对卧室温度、湿度、CO2浓度连续测量了一整晚,通过睡眠手环监测睡眠情况,通过问卷调查收集受试者入睡前和醒来后对卧室的环境评价,以及当晚睡眠情况的主观评价。结果发现:被调查卧室热环境良好,但近80%卧室平均CO2体积分数高于1 000×10-6。通过睡眠手环测量的客观睡眠指标与通过问卷获得的睡眠主观评价指标存在显著相关。室内CO2浓度与睡眠潜伏时长存在显著正相关。当室内空气质量评价越高时,受试者深度睡眠时间占比越高,入睡时间越短,入睡和起床越容易,对于睡眠总体满意度越高。该研究表明降低室内CO2浓度,提升室内空气质量评价,有利于改善睡眠质量。
关键词:卧室空气质量CO2浓度睡眠质量实测调研
作者简介:王梅,女,1996年生,硕士研究生;*张晓静(通信作者)100124北京市朝阳区北京工业大学绿色建筑环境与节能技术北京市重点实验室,E-mail:xjzhanger@163.com;
基金:国家自然科学基金青年项目(编号:51708006);北京市教委“高创计划”青年拔尖团队项目(编号:2017000026833TD02);
尊敬的用户,本篇文章需要2元,点击支付交费后阅读
参考文献[1] 李玉华,邵爱玉,毕先伟,等.环境对公共场所从业人员睡眠质量的影响[J].预防医学文献信息,2002(2):134-136.

[2] 张宇峰.热环境对睡眠的影响[J].暖通空调,2016,46(6):55-64.

[3] 李净,刘艳峰,宋聪,等.西北民居冬季睡眠被褥微气候研究[J].建筑科学,2016,32(2):68-72.

[4] BEKÖG,LUND T,NORS F,et al.Ventilation rates in the bedrooms of 500Danish children[J].Building and environment,2010,45(10):2289-2295.

[5] LIU W,HUANG C,SHEN L,et al.Associations between natural ventilation for the child's bedroom during night and childhood asthma in Shanghai,China[J].Procedia engineering,2015,121:501-505.

[6] KIM M,CHUN C,HAN J.A Study on bedroom environment and sleep quality in Korea[J].Indoor and built environment,2010,19(1):123-128.

[7] 中国疾病预防控制中心环境与健康相关产品安全所,中国环境科学研究院环境标准研究所,中国疾病预防控制中心辐射防护所,等.室内空气质量标准:GB/T18883-2002[S].北京:中国标准出版社,2002:4.

[8] SEPPANEN O A,FISK W J,MENDELL M J.Association of ventilation rates and CO2concentrations with health and other responses in commercial and institutional buildings[J].Indoor air,1999,9(4):226-252.

[9] LUO G,ZHANG X,XIE J,et al.Associations of indoor CO2concentration with sleep quality and other human responses[C]∥The International Symposium on Heating,Ventilation and Air Conditioning,2019:963-969.

[10] BUYSSE D J,REYNOLDS C F,MONK T H,et al.The Pittsburgh sleep quality index:a new instrument for psychiatric practice and research[J].Psychiatry research,1989,28(2):193-213.

[11] 李志辉,张紫燕,黄晓梅,等.环境物理因素对睡眠影响的研究进展[J].环境与健康杂志,2019,36(3):256-260.

[12] 潘黎,连之伟,兰丽.不同温度环境下的睡眠质量评价[C]∥上海市制冷学会2011年学术年会论文集,2011:495-501.

[13] GUNNARSEN L,FANGER P O.Adaptation to indoor air pollution[J].Environment international,1992,18:43-54.

[14] SUN W,CHEONG K W D,MELIKOV A K.Subjective study of thermal acceptability of novel enhanced displacement ventilation system and implication of occupants'personal control[J].Building and environment,2012,57:49-57.

[15] 中国建筑科学研究院.民用建筑供暖通风与空气调节设计规范:GB 50736-2012[S].北京:中国建筑工业出版社,2012:6.

[16] NIOSH.Pocket guide to chemical hazards:carbon dioxide[S].Washington DC:National Institute for Occupational Safety and Health,2005:1.

[17] ZAMBOTTI M,GOLDSTONE A,CLAUDATOSS,et al.A validation study of Fitbit Charge 2TMcompared with polysomnography in adults[J].Chronobiol international,2018,35(4):465-476.

[18] XIONG J,LAN L,LIAN Z W,et al.Associations of bedroom temperature and ventilation with sleep quality[J].Science and technology for the built environment,2020(5):1-13.

[19] OKANO K,KACZMARZYK J R,DAVE N,et al.Sleep quality,duration,and consistency are associated with better academic performance in college students[J].npj Science of learning,2019,4(1):1-5.

[20] STRØM-TEJSEN P,ZUKOWSKA D,WARGOCKIP,et al.The effects of bedroom air quality on sleep and next-day performance[J].Indoor air,2016,26(5):679-686.

[21] MISHRA A K,RUITENBEEK A,LOOMANS M,et al.Window/door opening-mediated bedroom ventilation and its impact on sleep quality of healthy,young adults[J].Indoor air,2018,28(2):339-351.
Effect of bedroom environment on sleep quality in Beijing during heating season
Wang Mei Zhang Xiaojing Luo Guanzhang Xie Jingchao Liu Jiaping
(Beijing University of Technology)
Abstract: In order to investigate the bedroom environment, sleep quality of residents and the association with bedroom environment and sleep quality, this study randomly investigates 48 households in the urban area of Beijing during the heating season. Bedroom environment parameters, including temperature, relative humidity and CO2 concentration, are recorded during the whole measured night. Objective sleep quality is measured by an actigraphy sensor. Subjective assessments on sleep quality and environmental perceptions are collected by paper-based questionnaires before and after sleep. The results indicate that the thermal and humid conditions of bedrooms during the measured night are in good condition. Nearly 80% of surveyed bedrooms have an average CO2 concentration above 1 000×10-6. There is a significant correlation between objective sleep quality measured by actigraphy sensor and subjective sleep quality collected by questionnaires. Indoor CO2 concentration is significantly and positively correlated with sleep onset latency. When bedroom air quality perception is higher, subjects have a higher deep sleep ratio and lower sleep onset latency, and they report feeling easier to fall asleep, easier to get up, and more satisfied with sleep. This study indicates that reducing indoor CO2 concentration and improving indoor air quality evaluation are beneficial to improve sleep quality.
Keywords: bedroom; air quality; CO2 concentration; sleep quality; field investigation;
642 0 0
文字:     A-     A+     默认 取消