国家电网某机房末端断水温升数值模拟与实测对比验证

作者:张乐丰 郑品迪 张林锋 黄冬梅 杨超 韩泽磊 李扬 林楠 宋杰 贾涛 冯睿
单位:国家电网有限公司信息通信分公司 北京瑞思博创科技有限公司
摘要:对国家电网某机房进行了末端空调水阀从关闭到开启整个过程的实测与数值模拟对比研究,结果表明:冷、热通道机柜前门上温度传感器的模拟平均误差分别为3.1%和3.6%,瞬态模拟温升的整体变化趋势一致;冷通道各个传感器的逐时平均误差最大值为13.88%,平均值为9.31%。经安全运行策略分析可知,提出的优化方案能保证冷通道传感器温升极限全部在32℃以下,数值模拟可以有效预测机房IT设备的温度上升情况,减少机房温升灾难事件的发生。
关键词:冷却故障机房温升速率数值模拟实测安全运行
作者简介:张乐丰,男,1986年生,博士研究生,高级工程师;*郑品迪(通信作者)100036北京市海淀区复兴路61号恒欣商务大厦302E-mail:zhengpindi@rainspur.com;
尊敬的用户,本篇文章需要2元,点击支付交费后阅读
参考文献 [1] PICO P,VALDÉS J,PINILLA A,et al.CFD modelling of the air conditioning system for a Tier 2 data centre [J].Advances in building energy research,2022,16(2):231- 261.

  [2] CHO J K,WOO J S,PARK B Y,et al.A comparative CFD study of two air distribution systems with hot aisle containment in high-density data centers [J].Energies,2020,13(22):1- 19.

  [3] FULPAGARE Y,JOSHI Y,BHARGAV A.Rack level transient CFD modeling of data center [J].International journal of numerical methods for heat & fluid flow,2018,28(2):381- 394.

  [4] 傅烈虎.数据中心冷却失效引起的机房温升研究[J].暖通空调,2017,47(2):63- 67,31.

  [5] 马昕宇,王军,杜垲.数据中心热环境瞬态CFD模拟与分析[J].制冷技术,2019(1):61- 66.

  [6] 秦冰月,郑匡庆,闫涛,等.数据中心多场景冷却系统失效研究[J].暖通空调,2021,51(10):145- 149.

  [7] 吕珂,李明江,李智刚.高功率密度数据机房无连续制冷的风险分析[J].电信工程技术与标准化,2014,27(7):41- 45.

  [8] 朱述振,邵安,宋伟男,等.满载机房冷源缺失后的环境温升及恢复分析:基于华东地区某数据中心的测试数据[J].洁净与空调技术,2021(4):123- 128.

  [9] 张明蕊.封闭冷通道的数据中心机柜温升规律的实验与机理研究[D].天津:天津大学,2020:46- 58.
Comparison and verification of numerical simulation and actual measurement of temperature rise of water cut-off at terminal in a machine room of the State Grid
Zhang Lefeng Zheng Pindi Zhang Linfeng Huang Dongmei Yang Chao Han Zelei Li Yang Lin Nan Song Jie Jia Tao Feng Rui
(State Grid Information & Communication Branch Beijing Rainspur Technology Co., Ltd.)
Abstract: For a machine room of the State Grid, a comparative study of the actual measurement and numerical simulation of the entire process from the closing to the opening of the air conditioning terminal water valve is carried out in this paper. The results show that the average simulation error of the temperature sensor on the front door of the cabinet in cold aisle and hot aisle is 3.1% and 3.6% respectively, and the overall change trend of the transient simulated temperature rise is consistent. The maximum hourly average error of each sensor in the cold aisle is 13.88%, and the average value is 9.31%. The analysis of safe operation strategy shows that the proposed optimization scheme can ensure that the temperature rise limit of cold aisle sensors is all below 32 ℃. The numerical simulation can effectively predict the temperature rise of IT equipment in the machine room and reduce the occurrence of temperature rise disaster events in the machine room.
Keywords: cooling failure; machine room; temperature rise rate; numerical simulation; actual measurement; safe operation;