中信技术研发基地项目冷热源及空调系统设计

作者:张亚立 劳逸民 潘云钢 李雯筠
单位:中国建筑设计研究院有限公司
摘要:介绍了中信技术研发基地生产运营楼和研发办公楼冷热源及空调系统设计。研发办公楼利用生产运营楼数据机房余热作为空调热源,空调系统采用温湿度独立控制系统;新风系统采用双盘管冷源,充分利用高温水能量,并利用室内排风对新风进行再热,防止结露。生产运营楼采用冷水机组作为冷源,数据机房空调系统采用高架空地板下送风形式,新风系统新风量按换气次数为0.8 h-1设计,冬夏季采用室内露点温度送风,控制室内湿度。生产运营楼数据机房实际运行工况下电能利用效率(PUE)为1.26。
关键词:冷热源余热回收空调系统温湿度独立控制双盘管冷源新风
作者简介:张亚立,女,1977年生,硕士研究生,教授级高级工程师,主任工程师100044北京市西城区车公庄大街19号院创新楼8层,E-mail:zhangyl@cadg.cn;
尊敬的用户,本篇文章需要2元,点击支付交费后阅读
参考文献[1] 潘云钢.基于溶液调湿处理新风的温湿度独立控制系统与常规空调系统设计能耗的比较分析[J].暖通空调,2011,41(5):5- 8,46.

[2] 北京市建筑设计研究院有限公司.公共建筑节能设计标准:DB 11/687—2015[S].北京:[出版者不详],2015:84- 86.

[3] 中国电子工程设计院.数据中心设计规范:GB 50174—2017[S].北京:中国计划出版社,2017:5.

[4] 张亚立,徐阳,金华国,等.双盘管冷源温湿度独立控制系统新风送风方式研究[J].暖通空调,2016,46(6):87- 90.
Design of cold and heat sources and air conditioning systems for CITIC technology research and development base project
Zhang Yali Lao Yimin Pan Yungang Li Wenjun
(China Architecture Design & Research Group)
Abstract: This paper presents the design of cold and heat sources and air conditioning systems in the production and operation building and the research and development office building of the CITIC technology research and development base. The research and development office building uses waste heat from the data room of the production and operation building as the air conditioning heat source, and the air conditioning system adopts a temperature and humidity independent control system. The outdoor air system adopts a double coil cold source, makes full use of high temperature water energy, and uses indoor exhaust air to reheat the outdoor air to prevent condensation. The chiller is used as the cold source in the production and operation building, and the air conditioning system of the data room adopts the form of air supply under the elevated floor. The outdoor air volume of the outdoor air system is designed according to the air change rate of 0.8 h-1. The indoor dew point temperature is used for the air supply temperature in winter and summer to control the indoor humidity. The actual power utilization efficiency(PUE) in the data room of the production and operation building is 1.26.
Keywords: cold and heat source; waste heat recovery; air conditioning system; temperature and humidity independent control; double coil cold source; outdoor air;