严寒地区新型空气源热泵新风机组性能研究

作者:张宇欣 魏文哲 常丽娜 倪龙 姚杨
单位:哈尔滨工业大学 寒地城乡人居环境科学与技术工业和信息化部重点实验室 无锡高新区科技创新促进中心
摘要:为保障建筑室内空气品质,解决严寒地区新风加热问题,提出将室内回风与新风混合,提高新风温度,再利用空气源热泵室内侧换热器加热混合空气的新型空气源热泵新风机组。针对哈尔滨冬季气象参数,采用理论与实验相结合的方法,对新风机组的系统形式、运行效果及节能性进行了分析。结果表明,新风机组能够在保证新风量和送风温度的条件下稳定运行,测试期间COP能够维持在3.0左右,最高达到4.3,具有良好的节能性和环保性。
关键词:新风机组新风加热空气源热泵严寒地区COP能耗分析
作者简介:张宇欣,女,1997年生,在读硕士研究生;*倪龙(通信作者)150090哈尔滨市南岗区黄河路73号哈工大寒地楼423-1,E-mail:nilonggn@163.com;
尊敬的用户,本篇文章需要2元,点击支付交费后阅读
参考文献[1] ZHOU F,DUAN W,MA G Y.Thermal performance of a pump-driven loop heat pipe as an air-to-air energy recovery device[J].Energy and buildings,2017,151:206- 216.

[2] 刘拴强,江亿,刘晓华,等.热泵驱动的双级溶液调湿新风机组原理及性能测试[J].暖通空调,2008,38(1):54- 59,63.

[3] OZYOGURTCU G,MOBEDI M,OZERDEM B.Techno-economic evaluation of a ventilation system assisted with exhaust air heat recovery,electrical heater and solar energy[J].Energy and buildings,2014,72:17- 23.

[4] FRACASTORO G V,SERRAINO M.Energy analyses of buildings equipped with exhaust air heat pumps (EAHP)[J].Energy and buildings,2010,42(8):4180- 4190.

[5] 冉春雨,陈傲雪,王春清.热泵热回收新风机在寒冷地区的实验研究[J].中国建设信息供热制冷,2009(8):48- 50.

[6] 黄凯良,姜编,冯国会.使用CO2空气源热泵回收建筑排风的节能效果分析[J].节能,2017,36(6):25- 27,2.

[7] 张文军.基于热泵的排风热回收系统实验研究[J].铁道工程学报,2014(6):114- 117.

[8] 石峰豪,卢军.热回收效率对排风热回收式热泵性能的影响研究[J].制冷与空调(四川),2020,34(1):6- 9,14.

[9] GE G M,XIAO F,XU X H.Model-based optimal control of a dedicated outdoor air-chilled ceiling system using liquid desiccant and membrane-based total heat recovery[J].Applied energy,2011,88(11):4180- 4190.

[10] 赵天怡,范朋丹,历秀明,等.基于独立新风系统的新风量保障方法及经济性研究[J].暖通空调,2019,49(10):97- 104.

[11] 杨灵艳,徐伟,李剑东,等.热泵型新风环境控制一体机性能测试工况研究[J].暖通空调,2020,50(8):48- 52,122.
Research on performance of a novel outdoor air handling unit with air-source heat pump in severe cold zone
Zhang Yuxin Wei Wenzhe Chang Lina Ni Long Yao Yang
(Harbin Institute of Technology Key Laboratory of Cold Region Urban and Rural Human Settlement Environment Science and Technology, Ministry of Industry and Information Technology WND Sci-tech Innovation Promotion Center)
Abstract: To ensure the indoor air quality and solve the problem of heating outdoor air in severe cold zone, a novel outdoor air handling unit with air-source heat pump is proposed, which mixes indoor return air and outdoor air to increase the temperature of outdoor air, and then uses the indoor side heat exchanger of the air-source heat pump to heat the mixed air. The system form, operation performance and energy-saving performance of the outdoor air handling unit are analysed through experimental and theoretical methods based on the meteorological parameters in Harbin in winter. The results show that the outdoor air unit could operate stably under the premise of ensuring the supply air temperature and the outdoor air rate. The COP remains around 3.0 and its maximum value reaches 4.3 during the test period. These indicate that the experimental unit has good performances in energy-saving and environmental protection.
Keywords: outdoor air unit; outdoor air heating; air-source heat pump; severe cold zone; COP; energy consumption analysis;
536 0 0