某酒店制冷机房运行策略优化

作者:刘乃玲 管乐宝 卞姗姗 邵东岳
单位:山东建筑大学 济南市市政工程设计研究院集团)有限责任公司 同圆设计集团股份有限公司
摘要:对华东地区某酒店制冷机房运行策略进行了优化,利用能耗模拟软件对多种运行方案进行了仿真分析。结果表明:原方案仅对冷水泵采用变频控制,制冷机房能效比为4.62;优化方案1采取传统变频方式,对冷水泵、冷却水泵、冷却塔风机采用变频控制,制冷机房能效比达到5.32,与原方案相比提升了15.1%;优化方案2通过对冷水机组、冷水泵、冷却水泵、冷却塔风机进行优化控制,制冷机房能效比为5.48,与原方案相比能效比提升了18.6%,且每年可减少约79 t碳排放量,节能效果显著。
关键词:高效制冷机房运行策略优化节能能耗模拟能效比碳排放
作者简介:刘乃玲,男,1966年生,工学博士,教授;*管乐宝(通信作者),250101山东省济南市历城区凤鸣路1000号山东建筑大学,E-mail:guanlebao0303@163.com;
尊敬的用户,本篇文章需要2元,点击支付交费后阅读
参考文献[1] 孙锐,崔红社,李言永,等.青岛市既有办公建筑冷源系统运行调研分析[J].建筑热能通风空调,2022,41(7):40- 43,84.

[2] 邹惠芬,魏冉,宫丽红,等.公共建筑空调系统能耗分析及节能改造[J].沈阳建筑大学学报(自然科学版),2017,33(4):738- 743.

[3] 周伟业.五星级酒店建筑能耗水平及节能潜力分析[D].天津:天津大学,2016:45- 57.

[4] YU F W,CHAN K T.Economic benefits of optimal control for water-cooled chiller systems serving hotels in a subtropical climate[J].Energy and buildings,2010,42(2):203- 209.

[5] 王香兰,晋欣桥,吕远,等.基于关联规则的多冷水机组系统负荷优化分配[J].制冷学报,2022,43(1):35- 45.

[6] CHAN K C,WONG V T T,YOW A K F,et al.Development and performance evaluation of a chiller plant predictive operational control strategy by artificial intelligence[J].Energy and buildings,2022,262:112017.

[7] 何恒钊,屈国伦,谭海阳,等.广州白天鹅宾馆改造工程暖通空调系统绿色节能设计[J].暖通空调,2016,46(1):33- 37.

[8] 中国建筑科学研究院.民用建筑供暖通风与空气调节设计规范:GB 50736—2012[S].北京:中国建筑工业出版社,2012:5- 10.

[9] ASHRAE.ASHRAE handbook:HVAC applications[J].IP ed.Atlanta:ASHRAE Inc.,2011:42.1- 42.44.

[10] 文先太,孙国平,陈春蕾.大型离心式冷水机组变工况性能分析与试验研究[J].制冷与空调,2018,18(6):81- 84.

[11] 李龙.空调冷却水系统变频节能分析[J].暖通空调,2020,50(8):65- 69.

[12] 丁欣之,胡传阳,刘晓静,等.苏南地区典型高星级酒店建筑能耗调研及节能潜力分析[J].江苏建筑,2020(增刊1):90- 93.

[13] 中国建筑科学研究院有限公司,中国建筑标准设计研究院有限公司.建筑碳排放计算标准:GB/T 51366—2019[S].北京:中国建筑工业出版社,2019:8- 9.
Optimization of operation strategy for chiller room in a hotel
Liu Nailing Guan Lebao Bian Shanshan Shao Dongyue
(Shandong Jianzhu University Jinan Municipal Engineering Design &Research Institute (Group) Co., Ltd. Tong Yuan Design Group)
Abstract: In this paper, the operation strategy of a hotel chiller room in East China is optimized, and a variety of operation schemes are simulated and analysed by using energy consumption simulation software. The results show that the original scheme only uses the frequency conversion control for the chilled water pumps, and the energy efficiency ratio of the chiller room is 4.62. Optimization scheme 1 adopts the traditional frequency conversion method and adopts frequency conversion control for the chilled water pumps, cooling water pumps and cooling tower fans. The energy efficiency ratio of the chiller room reaches 5.32, which is increased by 15.1% compared with the original scheme. Optimization scheme 2 optimizes the control of the chillers, chilled water pumps, cooling water pumps and cooling tower fans, the energy efficiency ratio of the chiller room is 5.48, which is 18.6% higher than that of the original scheme, the annual carbon emissions can be reduced by about 79 t, and the energy saving effect is remarkable.
Keywords: high efficiency chiller room; optimization of operation strategy; energy saving; energy consumption simulation; energy efficiency ratio; carbon emission;
99 0 0