摘要:对于夏热冬冷地区的两管制空调水系统,输配管网和末端根据夏季工况确定。在确定的电价政策下,冬季的供回水温差越大,节能性和经济性越好,但受末端换热设备构造对水流状态要求的影响,供回水温差不能无限增大。结合节能要求、层流雷诺数、末端换热设备换热系数及两管制系统阀门的调节精度,以上海某实际项目为例,采用试算法得到该工程的冬季空调供回水温差范围为10~25℃,可供类似工程设计参考。
关键词:两管制冬季供热供回水温差层流换热系数可调比阀权度
作者简介:蒋晓杰,男,1987年生,大学,工程师200002上海市黄浦区汉口路151号华东建筑设计研究院有限公司E-mail:jxjl9559@ecadi.com;
尊敬的用户,本篇文章需要2元,点击支付交费后阅读
参考文献参考文献

[1] 中国建筑科学研究院.民用建筑供暖通风与空气调节设计规范:GB 50736—2012[S].北京:中国建筑工业出版社,2012:71-91.

[2] 赵荣义,范存养,薛殿华,等.空气调节[M].3版.北京:中国建筑工业出版社,2008:92-93.

[3] 陆耀庆.实用供热空调设计手册[M].2版.北京:中国建筑工业出版社,2008:1574-1576.

[4] 沈列丞,马伟骏.空调水系统中电动调节阀流量特性研究[J].暖通空调,2011,41(12):15-20.

[5] 曹文斌.调节阀流量特性及动态性能研究[D].兰州:兰州理工大学,2013:20-25.

[6] 罗伯特·珀蒂琼.全面水力平衡暖通空调水力系统设计与应用手册[M].杨国荣,胡仰耆,魏炜,等,译.北京:中国建筑工业出版社,2017:119-120.
Discussion on temperature difference range between heating supply and return water of two-pipe air conditioning water systems
Jiang Xiaojie Xiao Sun Zuo Xin
(East China Architectural Design and Research Institute Co., Ltd.)
Abstract: For the two-pipe air conditioning water system in hot summer and cold winter zone, the transmission and distribution pipe network and the terminal are determined according to the summer working conditions. Under the determined electricity price policy, the greater the temperature difference between the supply and return water in winter is, the better the energy saving and economy is, but due to the influence of the structure of the terminal heat exchange equipment on the water flow state requirements, the temperature difference between the supply and return water cannot be increased indefinitely. Combined with the energy saving requirements, the laminar flow Reynolds number, the heat exchange coefficient of the terminal heat exchange equipment and the adjustment accuracy of the valve of the two-pipe system, taking a practical project in Shanghai as an example, the temperature difference of 10 to 25 ℃ between the winter air conditioning supply and return water of the project is obtained by using the test algorithm, which can be used as a reference for similar engineering designs.
Keywords: two-pipe; heat supply in winter; temperature difference between supply and return water; laminar flow; heat exchange coefficient; adjustable ratio; valve authority;