积尘对板式换热器性能影响的实验研究

作者:霍雨霞 于震 张宏葛 赵嘉琪
单位:成都基准方中建筑设计有限公司北京分公司 天津城建大学 北京科兴中维生物技术有限公司
摘要:通过实验对颗粒物在新风换气机换热器表面的沉积规律及积尘对换热器性能的影响进行了研究。结果表明:对于相同结构的换热器,风量越大,相同粒径颗粒物的沉积分数越小;风量为250~350 m3/h时,在0.3~10.0μm粒径范围内,颗粒物的沉积分数随着粒径的增大而增大;随着运行时间的增加,积尘量增大,积尘30、70 d后,换热器的平均全热交换效率比未积尘时分别降低2.314%和5.613%。对减少颗粒物在换热器表面的沉积提出了建议。
关键词:新风换气机板式换热器换热性能积尘颗粒物沉积规律全热交换效率
作者简介:霍雨霞,女,1989年生,硕士研究生,工程师100123北京市昌平区回龙观街道龙旗广场6号楼4单元2105,E-mail:HYX_CH@163.com;
尊敬的用户,本篇文章需要2元,点击支付交费后阅读
参考文献[1] WARING M S,SIEGEL J A.Particle loading rates for HVAC filters,heat exchangers,and ducts[J].Indoor air,2008,18:209- 224.

[2] LI Y,JAMES E B,ECKHARD A G.The impact of fouling on the performance of filter-evaporator combinations[J].International journal of refrigeration,2007,30:489- 514.

[3] LANKINEN R,SUIHKONEN J,SARKOMAA P.The effect of air side fouling on thermal-hydraulic characteristics of a compact heat exchanger[J].International journal of energy research,2003,27:349- 361.

[4] YOUNG-CHULL A,JAE-MIN C,HEE-SOO S,et al.An experimental study of the air-side particulate fouling in fin-and-tube heat exchangers of air conditioners[J].Korean journal of chemical engineering,2003,20(5):873- 877.

[5] MUYSHONDT A,NUTTER D,GORDON M.Investigation of a fin-and-tube surface as a contaminant sink[C]//ASHRAE IAQ 98,1998:207- 211.

[6] CHIDAMBARAM N,DJAMEL L,LORENZO B,et al.Mechanisms of particle deposition in a fully developed turbulent open channel flow[J].Physics of fluids,2003,15(3):763- 774.

[7] 中国建筑科学研究院.空气-空气能量回收装置:GB/T 21087—2007[S].北京:中国标准出版社,2007:1- 10.

[8] 王玉婕,强天伟.室内可吸入颗粒物的来源及其防治措施探讨[J].洁净与空调技术,2011(4):70- 72.

[9] 陈建华,王玮,刘红杰,等.北京市交通路口大气颗粒物污染特征研究(I):大气颗粒物污染特征及其影响因素[J].环境科学与研究,2005,18(2):34- 37.
Experimental study on effect of dust deposition on performance of plate heat exchangers
Huo Yuxia Yu Zhen Zhang Hongge Zhao Jiaqi
(Beijing Branch of Chengdu Benchmark Fangzhong Architectural Design Co., Ltd. Tianjin Chengjian University Sinovac Life Sciences Co., Ltd.,Beijing)
Abstract: The deposition law of particles on the surface of heat exchanger of outdoor air ventilators and the effect of dust deposition on the performance of heat exchangers are studied by experiments. The results show that for the heat exchangers with the same structure, the larger the air volume is, the smaller the deposition fraction of particles with the same particle size is. When the air volume is 250 to 350 m3/h, the deposition fraction of particles increases with the increase of particle size in the particle size range of 0.3 to 10.0 μm. With the increase of operating time, the amount of dust deposition increases. After 30 and 70 days of dust deposition, the average total heat exchange efficiency of the heat exchanger decreases by 2.314% and 5.613% compared with that in the clean state, respectively. Some suggestions are put forward to reduce the deposition of particles on the surface of the heat exchanger.
Keywords: outdoor air ventilator; plate heat exchanger; heat transfer performance; dust deposition; particle; deposition law; total heat exchange efficiency;