贵阳某数据中心多种空调形式的应用分析

作者:王晨平 魏俊旗 吴玲 王克勇 陈璐
单位:中通服咨询设计研究院有限公司
摘要:以贵阳某数据中心为研究载体,通过对工程概况、气候条件、资源条件、空调原理和技术方案的分析,对比探究了各空调方案的机柜出架数量、节能性和经济指标。结果表明:磁悬浮蒸发相变冷却空调方案建设投资高,但能够大幅度提高机柜出架数量和项目收益;该空调系统全年耗电量较少,但水资源消耗大。间接蒸发冷却空调方案的节能性最优,但是机柜出架数量最少,单位功耗造价高,利润率低。水冷式冷水空调方案节能性差,机柜出架数量较少,但建设投资低。
关键词:数据中心空调水冷式冷水系统间接蒸发冷却磁悬浮蒸发相变制冷负载因子CLF)水资源利用效率WUE)
作者简介:王晨平,男,1993年生,硕士研究生,工程师,210019江苏省南京市建邺区楠溪江东街58号中通服咨询设计研究院有限公司,E-mail:1610243489@qq.com;
尊敬的用户,本篇文章需要2元,点击支付交费后阅读
参考文献[1] 中国信息通信研究院.数据中心白皮书(2022)[EB/OL].[2022-12-15].https://www.sgpjbg.com/baogao/69430.html.

[2] 赵磊,李宏鹏.长三角地区某数据中心空调系统设计[J].暖通空调,2020,50(1):86- 91.

[3] 中国电子工程设计院.数据中心设计规范:GB 50174—2017[S].北京:中国计划出版社,2018:34- 40.

[4] 唐瑞,熊汉兵,杨艳,等.武汉某数据中心空调系统设计及节能分析[J].暖通空调,2022,52(5):96- 101,35.

[5] 中国标准化研究院.数据中心能效限定值及能效等级:GB 40879—2021[S].北京:中国标准出版社,2021:2.

[6] 国德防,祝建军.数据中心机房中央空调解决方案:磁悬浮变频离心式机组在数据中心机房中的应用[C]//第七届中国制冷空调行业信息大会论文集,2014:201- 107.

[7] 张国林,夏春华,王培,等.张北某数据中心空调系统设计[J].暖通空调,2019,49(4):92- 96,127.

[8] 马钢,黄翔,杜妍,等.数据中心用蒸发冷却空气处理机组适用性及能耗分析[J].制冷与空调,2022,22(4):91- 96.

[9] 张忠斌,邵小桐,宋平,等.数据中心能效影响因素及评价指标[J].暖通空调,2022,52(3):148- 155,99.
Application analysis of various air conditioning forms in a data center in Guiyang
Wang Chenping Wei Junqi Wu Ling Wang Keyong Chen Lu
(China Information Consulting & Designing Institute Co., Ltd.)
Abstract: This paper takes a data center in Guiyang as the research carrier. Through the analysis of the project overview, climate conditions, resource conditions, air conditioning principle and technical scheme, the number of cabinets, energy conservation and economic indicators of each air conditioning scheme are explored and compared. The results show that the construction investment of the maglev evaporative phase change cooling air conditioning scheme is high, but it can greatly improve the number of cabinets and the project income. This air conditioning system consumes less electricity throughout the year, but the water consumption is large. The indirect evaporative cooling air conditioning scheme has the best energy conservation, but the number of cabinets is the least, the unit power consumption cost is high, and the profit rate is low. The water-cooled chilled water air conditioning scheme has poor energy conservation and less number of cabinets, but the construction investment is low.
Keywords: data center; air conditioning; water-cooled chilled water system; indirect evaporative cooling; maglev evaporative phase change; cooling load factor(CLF); water usage effectiveness(WUE);