密拼叠合板接缝处直剪性能研究及工程应用

引用文献:

邓世斌 ,董博, 毕琼, 蔚博琛, 雷雨, 吴靖 ,许明姣. 密拼叠合板接缝处直剪性能研究及工程应用[J]. 建筑结构,2022,48(13):7-14.

DENG Shibin, DONG Bo, BI Qiong, WEI Bochen, LEI Yu, WU Jing ,XU Mingjiao. Research and engineering application on direct shear performance at the joint of composite slab connected without gaps[J]. Building Structure,2022,48(13):7-14.

作者:邓世斌 ,董博, 毕琼, 蔚博琛, 雷雨, 吴靖 ,许明姣
单位:中国建筑西南设计研究院有限公司
摘要:通过11块密拼叠合板试件的单向拟静力试验,对接缝处的平面内直剪承载力进行了研究;同时使用分层壳单元,对密拼叠合板水平荷载作用下的平面内直剪承载力、竖向荷载作用下的导荷方式等进行了数值分析。结果表明:密拼叠合板平面内直剪承载力随后浇层厚度、接缝处连接钢筋配筋率的增大而增大;竖向荷载作用下,密拼叠合板在弹性阶段,竖向导荷可等同于现浇板,但承载力计算时跨中和支座弯矩需进行调整;长期荷载作用下其挠度可取现浇板挠度值乘以不小于1.1的增大系数。最后,将研究成果应用于密拼叠合板的设计实践中。
关键词:叠合板;密拼整体式接缝;接缝传力机理;平面内直剪承载力;拟静力试验
作者简介:邓世斌,硕士,高级工程师,一级注册结构工程师,主要从事装配式建筑结构抗震等研究,Email:29383509@qq.com。董博,硕士,高级工程师,主要从事装配式建筑结构抗震等研究,Email:514146502@qq.com。
基金:“十三五”国家重点研发计划项目(2016YFC0701900)。
尊敬的用户,本篇文章需要2元,点击支付交费后阅读
参考文献[1] 装配式混凝土结构技术规程:JGJ 1—2014[S].北京:中国建筑工业出版社,2014.
[2] 装配式混凝土建筑技术标准:GB 51231—2016[S].北京:中国建筑工业出版社,2017.
[3] 吴方伯,刘彪,李钧,等.新型叠合板拼缝构造措施的试验研究及有限元分析[J].工业建筑,2015,45(2):50-56.
[4] 刘运林.双向叠合板接缝处受力机理试验研究与数值模拟[D].合肥:合肥工业大学,2014.
[5] 余永涛,赵勇,高志强.单缝密拼钢筋混凝土叠合板受弯性能试验研究[J].建筑结构学报,2019,40(4):1-9.
[6] 张敬书,倪永松,姚远,等.不同拼缝方向的预制带肋底板混凝土叠合板面内受力性能[J].土木工程学报,2015,48 (5):23-34.
[7] 林峰,欧智星,卢海霞.截面预裂的RC构件直剪与斜剪承载力比较[J].建筑结构,2014,44(19):75-80.
[8] 预制装配整体式钢筋混凝土结构技术规范:SJG 18—2009[S].深圳:深圳市住房和城乡建设局,2009.
[9] 建筑抗震试验规程:JGJ/T 101—2015[S].北京:中国建筑工业出版社,2015.
[10] Building code requirements for structural concrete:ACI 318-14[S].Farmington Hills,MI:American Concrete Institute,2014.
[11] PCI Design handbook(7th Edition):PCI[S].Chicago:Precast/Prestressed Concrete Institute,2010.
[12] European Committee for Standardization.Eurocode 2:design of concrete structures-part 1-1:general rules and rules for buildings:BS EN 1992-1-1[S].London:Standards Policy and Strategy Committee,2004.
Research and engineering application on direct shear performance at the joint of composite slab connected without gaps
DENG Shibin, DONG Bo, BI Qiong, WEI Bochen, LEI Yu, WU Jing ,XU Mingjiao
(China Southwest Architectural Design and Research Institute Co., Ltd.)
Abstract: Through the one-way pseudo-static test of 11 composite slabs connected without gaps specimens, the in-plane direct shear bearing capacity of the joints was studied. At the same time, the layered shell element was used to carry out numerical analysis of the in-plane direct shear bearing capacity of composite slab connected without gaps under horizontal load and the way of guiding the load under vertical load. The results show that the direct shear bearing capacity in the plane of the composite slab connected without gaps increases after the thickness of the pouring layer and the reinforcement ratio of the connecting steel bar at the joint increase; under the action of vertical load, the composite slab connected without gaps is in the elastic stage, and the vertical guided load can be equivalent to cast-in-place slab, but the bending moments of the mid-span and the support need to be adjusted when the bearing capacity is calculated; under long-term load, its deflection can be taken as the deflection of the cast-in-place slab multiplied by an increase factor not less than 1.1. Finally, the research results are applied to the design practice of composite slab connected without gaps.
Keywords: composite slab; monolithic joint connected without gaps; mechanism of joint force transfer; in-plane direct shear bearing capacity; pseudo-static test
432 0 0
文字:     A-     A+     默认 取消